Economic type motor protector BRN-M401
Protection function
* long time start * * time limit blocking protection overload protection
* inverse time overload protection * underload protection * grounding protection
* * leakage protection over voltage / low voltage * phase
* * * unbalanced phase sequence error external fault
Other characteristics
* the comprehensive parameter measuring motor, electric power measuring * motor start control
* 12 switch input * split design
* line four character LCD display * 0 (4) -20mA analog output
* power choose AC or DC
* 485 communication interface, Modbus-RTU or Profibus-DP protocol optional
The main purposes
* * motor comprehensive protection of various starting mode
Schematic wiring diagram:
ABN-M401经济型电动机电机保护器
保护功能
* 启动时间过长 * 堵转保护 * 定时限过载保护
* 反时限过载保护 * 欠载保护 * 接地保护
* 漏电保护
其它特性
* 电机各相电流测量 * 分体式设计
* 两行字符型LCD显示 * 简易双键查询及设定参数
* 5路状态量输入,4路继电器输出 * 0(4)-20mA模拟量输出
* 电源任意选择AC或DC
* 485通讯接口,Modbus-RTU 或Profibus-DP规约可选
主要用途
* 取代常规热继电器 * 低压电动机的电流型保护
原理接线图:
尺寸图:Size
BRN-M4口口-V口-I口-D口-M口-口
M- Modbus
P-profibus 通讯方式Communication methods
M0不选配模拟量输出功能 No analog output function
M4-4-20mA
M5-0-5V
D0-不选配漏电保护功能 No leakage protection function
D1-选配漏电保护功能 It have leakage protection functionI1-1A
电流规格 Current specification
I5-5A
I30-30A
I160-160A
备注::当电流大于160A时,需外配电流互感器,
在电流规格中直接注明电流变比即可
例如:电机为90KW,额定电流为180A,需在外部配置200/5电流互感器,
此时在电流规格中注明200/5即可
Note: : when the current is larger than 160A, need outside CT,
directly indicate CT variable ratio in the current specifications
For example: the 90KW motor rated current is 180A, need outside CT 200/5 ,
indicate CT variable ratio 200/5 in current specifications
V400-380V 额定电压 Rate Voltage
V600-660V
V0(M401无电压功能) M401 no voltage input function
M401 电动机保护控制器型号 MOTOR PROTECTOR MODEL
M403 电动机保护控制器型号 MOTOR PROTECTOR MODEL
电动机额定功率与电流规格选型 The motor rated power and current specification selection
CT规格 Current specification selection
|
电流范围 Current range
|
电动机功率The motor rated power
|
Inside CT 1A
|
0.5~1A
|
0.18~0.37KW
|
Inside CT 5A
|
1~5A
|
0.37~2.5KW
|
Inside CT 30A
|
5~30A
|
2.5~11KW
|
Inside CT 160A
|
30~160A
|
11~75KW
|
Outside CT 200/5A
|
100~200A
|
75~90KW
|
Outside CT 300/5A
|
200~300A
|
90~160KW
|
Outside CT 400/5A
|
300~400A
|
160~200KW
|
Outside CT 500/5A
|
400~500A
|
200~250KW
|
Outside CT 600/5A
|
500~600A
|
250~315KW
|
Outside CT 800/5A
|
600~800A
|
315KW以上
|