RTU GE-harris D25 measurement and control products

 

This document describes the characteristics and functions of electric power automation products --D25 multifunctional intelligent electronic device.
1 Introduction remote RTU control GE-harrisD25 device
GE-Harris company has been in SCADA system and electric power automation technology forefront. Harris is used in the manufacturing of substation control system of D20 series, in the SCADA system in the application of open architecture and distributed processing characteristics known. D20 through the application in the global power generation, substation and distribution, successfully demonstrated that the GE-Harris advanced engineering technology. However, in order to make the substation and distribution operation is more suitable for the power user requirements. The research and development of GE-Harris remains dedicated to more advanced technology.
D25 multifunctional intelligent electronic device is used for distributed remote terminal unit substation and substation.
D25 is a I/O module and communication product distribution, an intelligent, it is a basic and very important part of substation automation and control system. The product of the scalability and configurability makes it is economic and practical, at the same time, it provides a good solution for automatic application of large capacity.
The difference of substation automation product D25 and now use the RTU technology, the difference between it and RTU technology are as follows:
- instead of transmitter
Programmable logic control can be integrated (PLC)
- non billing meter
- Measurement and fault detection
- protective control
- sequence control
- operation locking
- power quality measurement
- protective function
D25 may be quantified through. Flexible input / output selection and application of powerful software to realize these functions. D25 support:
- up to 96 state input
- up to 16 control output of
- up to 16 analog input
Communication interface - the external system (D. 20, Ethernet or RS-232/RS-485)
Serial interface - two and external substation intelligent electronic equipment communication
- two maintenance configuration interface
- a received universal time code interface information
- the three auxiliary control / general digital output

 

6 additional functions of D25 software application can use additional to achieve stronger function.
6.1 programmable logic control
Logic programming using Harris, D25 can be configured to programmable logic control function. The programming and development of logic programming allows logic, for D25 sequence, algorithm. These algorithms can be used with any data in the D25 database, including the peripheral I/O and IED information. The algorithm is available on the host or sub station through the WESMAINT port passive initialization and / or pause.
6 2 protection
IDMT (as opposed to limit definition) multiple requirements of operation time and the flow peak is inversely proportional to. Can be set through the configuration of the configuration time magnitude. Dial to set the constant and US or IEC curve equation.
Sequence element is used for fault detection includes the number and direction, but only the number of output and the fault detection alarm set.
6.3 network support
When using the XCOM Ethernet module, D25 supports the following network standard and specification:
TCP/IP (terminal control program / Internet Protocol)
- SNMP
- ARP RARP (automatic recovery program)
- telephone network ASC (automatic synchronous control)
Network support allows download or upload D25 configuration data or fault data file and the IED configuration data, in fact also supports D25 and related IED.
6.4 communication protocol
Harris has a more than 75 communication protocol extensible protocol library and the main station of the IED communication protocol is used, and can be integrated in D25.
6 5 other applications
With many other SCADA and automation applications, such as substation load report, calculator and mailbox function
7 maintenance and configuration
D25 provides the user the local or distant on the system configuration or maintenance.
7.1 maintenance port
WESMAINT is on board maintenance port, the user can be PC connected to the D25DAC module WESMAINT port up operation. At the same time also supports remote dial. Through the WESMAINTT user can perform
The following diagnosis procedures:
- monitoring and change all state and simulated point real time state
- monitor D25 state and display any alarm condition
- print including alarm description. Points. The date and the nearest millisecond time record
SOE data - single point monitoring.
WESMAINT port support:
- password protection
D-9 hole joint, pin output is defined by data terminal equipment and in line with the 9 core IBM PC serial standards.
Fixed rate - 9600 Potter
- support asynchronous byte protocol.
7.2 D25 display
D25 monitor is used to perform diagnostic procedures local maintenance terminal (similar to the WESMAINT series M module). It has a 16 bit LCD display and a keyboard with 8 keys. D25 display module can be installed in the distance.
7.3 ConfigPro
The configuration system of D25 using the Hrarris ConfigPro configuration. ConfigPro in connection with the WESMSMAINT interface of the IBM compatible operating on PC. Using ConfigPro you can complete the following matters:
- to modify the D25 system path
- report generation system, such as the connection table. The peripheral configuration and project equipment data
- Preparation, edit, upload and download configuration
- perform maintenance tasks.
8 physical characteristics
The 8.1 housing
16.5 "casing size 1 option X4" x3. 5 "(length x width x height), for the" standard "gauge panel installation.
Option 2, 3 and 4 with 19 "mounting bracket, with internal" bracket and stack and a terminal board with the.
8.2 field wiring
The 8.21 state input
Field status input terminal plate is 0.375 inches (9 53mm) #6-32 partition, suitable for #10AWG (6mm2) rated voltage with wiring piece wire and 600VDC.
8 of 2.2 control output
Scene control output terminal board is 0.375 inches (9 53mm) #6-32 partition, suitable for #10AWG (6mm2) rated voltage with wiring piece wire and 600VDC.
8 2.3 analog input
Scene simulation input terminal on the terminal board is 0.375 inches (9 53mm) #6-32 partition, suitable for #10AWG (6mm2) rated voltage with wiring piece wire and 600VDC.
8 the 2.4 auxiliary control output
Field curing control output terminals in the D25DAC is 0.2 inches (5 08mm) of the wiring board austerity type, suitable for #12AWG (4mm2) rated voltage wires and 300VDC.
8 of 2.5 power supply
The power supply input terminal of the D25DAC is a 0.2 inch spacing austerity type wiring board, suitable for #12AWG (4mm2) rated voltage wires and 300VDC.
9 standard and protection
In all combinations, D25 reaches or exceeds the following requirements:
IEC255-5 insulation / isolation: 2500VRMS (3500VDC); >10Mohm, 500VDC
IEC255-4 pulse / voltage: 5KV (1 2/50 s) 0 5J
- power frequency: 250VRMS/500VRMS
IEC-255-22-1 high frequency interference: 2 5kV (1Mhz/400Hz)
IEC 801-4 high speed transient phenomena: 4KV (2 5Mhz/15ms/300ms); 2KV (5 0kHz/15ms/300ms)
IEEE C37. 90 1-1989 SWC and the high speed transient phenomenon: 2 5kV (1MHz/60Hz); 5kV (10/150ns/60Hz)
- IEC 801-5 - Volatility: 4kV (1 2/50 s) 2KA (8/20 s)
IEC 1000-4-1 - ring wave: 4kV (100KHz)
IEC 801-2 electrostatic discharge: 8Kv contact discharge; 15kV air discharge
IEC 801-3/IEEE C37. 90 2-1987RFI/EMI sensitivity: 10V/m (50kHz-1GHz)
IEC power frequency magnetic field: 100A/m (Continued); 1KA/m (1-3s)
- IEC 100-4-10 buffer oscillating magnetic field: 100A/m (1MHz)
- IEC 801-6 conducted disturbance: 9kHz-230MHz
CISPR 22ClassA, FCC Part 15 Class A radiation radiation
IEC 68-2-2 dry: +70 C
IEC68-2-1 cold: -40 C
IEC68-2-30 heat: +40 C, 70%RH; <=95%RH non condensing
IEC68-2-6 vibration
- IEC68-2-31 decreased and imbalance
IEC 8014, Level4; high speed transient phenomena and all I/O cable clamp coupling 60s
- EN 50081-2
- EN 50082-2
10 performance
When the maximum configuration does not exceed the following standards, the operation of D25 can achieve the best level;
- a network or the two SCADA protocols for high speed operation
- two IED interface running at high speed
- the clock input operation
100ms has 96 state input 128 events
In the 1 cycle, two pulse accumulator input operation
In 50ms, the 12 AC analog input change (such as the 3 vanishing voltage, 9 flow)
- 5ms after a control output; in the other 45ms after a control output; after 50ms and a control output
Alarm - 100ms 55 limit and fault simulation
- fault recording operation
The analog quantity event report of operation
- programmable algorithm of scan rate of 2 5MS (Boolean)

 

 

本文件描述了电力自动化产品--D25多功能智能电子装置的特性和功能。

1.  简介 远动RTU测控GE-harrisD25装置

GE-Harris公司一直处于SCADA系统和电力自动化技术的前列。Harris生产的用于变电站控制系统的D20系列,以其在SCADA系统应用中的开放式结构和分布处理的特点而著称。D20通过在全球的发电、变电及配电中应用,成功地证明了GE-Harris先进的工程技术。尽管如此,为了使变电和配电的操作更加适应于电力用户的要求。GE-Harris仍然致力于更先进的技术的开发和研究。

D25多功能智能电子装置是用于变电站远动终端和变电站的分布式单元。

D25是一个智能的、分布I/O模块和通讯产品,它是变电站自动化和控制系统的一个基本的且极其重要的部分。该产品的可扩展性与可组态性使得它经济实用,同时,给大容量的自动化应用提供了一个很好的解决方法。

D25与现在使用的RTU技术的变电站自动化产品有所区别,它与RTU技术的区别如下:

代替变送器

集成的可编程逻辑控制(PLC)

非计费表计

故障测量和检测

保护控制

顺序控制

操作闭锁

电质量测量

保护功能

D25通过可量化. 灵活的输入/输出选择及功能强大的软件的应用来实现这些功能。D25支持:

最多96个状态量输入

最多16个控制量输出对

最多16个模拟量输入

外部系统的通讯接口(D. 20,以太网或RS-232/RS-485)

两个与外部变电站智能电子设备通讯的串行接口

两个维护组态接口

一个接收通用时间码信息的接口

三个辅助控制/一般的数字输出

 6.  附加功能   D25可以使用附加的软件应用以达到更强的功能。

6. 1 可编程逻辑控制

使用Harris的逻辑编程,D25可以被结构成可编程逻辑控制功能。逻辑编程允许对D25进行逻辑、顺序、算法的编程和开发。这些算法可以使用D25 数据库中的任何数据,包括外设I/OIED信息。算法可以在主机上或子站通过WESMAINT口被动初始化和/或暂停。

6. 2. 保护

IDMT(反对限定义)要求操作时间与过流时峰值的倍数成反比。可通过组态设置组态时间的量值. 拨号设置常量和USIEC曲线方程。

顺序元件用于故障检测包括数量和方向,但只有数量输出和对故障检测报警设定。

6. 3 网络支持

当使用以太网XCOM模块,D25支持以下网络标准和规约:

TCP/IP(终端控制程序/网间协议)

SNMP

ARP RARP(自动恢复程序,)

电话网ASC(自动同步控制)

网络支持允许下载或上装D25组态数据或故障数据文件和IED组态数据,实际上也同时支持D25和相关的IED

6. 4 通讯规约

Harris有一个超过75个通讯规约的可扩展规约库,这些规约用于主站IED通讯,并且可在D25中集成。

6. 5. 其它应用

具有许多其它SCADA和自动化应用,如变电站负载报告,计算器和邮箱功能

7.  维护与组态

D25提供用户当地或远方对系统组态或维护。

7. 1 维护口

WESMAINT是板上维护口,用户可将PC接在D25DAC模块的WESMAINT口上来进行操作。同时也支持远方拨号。通过WESMAINTT用户可执行

以下的诊断程序:

监测和更改所有状态和模拟点的实时状态

监测D25的状态并显示任何报警条件

打印包括报警描述. 点数. 日期和最近的毫秒时间的记录

监测单独点的SOE数据。

WESMAINT口支持:

密码保护

D-9孔接头,针输出是由数据终端设备定义并且符合9IBM PC串口标准。

固定的9600波特的速率

支持异步字节规约。

7. 2 D25显示器

D25显示器是用于执行诊断程序的当地维护终端(WESMAINT M系列模块相似)。它有一个16LCD显示和一个8键键盘。D25显示模块可在远方安装。

7. 3 ConfigPro

D25使用HrarrisConfigPro的组态系统来组态。ConfigPro在与WESMSMAINT接口连接的IBM兼容PC机上运行。使用ConfigPro用户可以完成以下事项:

修改D25系统路径

生成系统报告,如接线表. 外设组态以及项目设备数据

编制、编辑、上装和下载组态

执行维护任务。

8.  物理特性

8. 1 外壳

选项1的外壳尺寸16. 5"x4"x3. 5"(xx),适合“标准”的表计屏面安装。

选项234带有19"的安装支架,具有内部“支架和堆栈”并且带有的端子板。

8. 2 现场接线

8. 21 状态输入

端子板上的状态输入的现场端子为0. 375英寸(9. 53mm)#6-32间隔板,适合#10AWG(6mm2 )带接线片的导线和600VDC的额定电压。

8. 2. 2 控制输出

端子板上的控制输出的现场子为0. 375英寸(9. 53mm)#6-32间隔板,适合#10AWG(6mm2 )带接线片的导线和600VDC的额定电压。

8. 2. 3 模拟输入

端子板上的模拟输入的现场端子为0. 375英寸(9. 53mm)#6-32间隔板,适合#10AWG(6mm2 )带接线片的导线和600VDC的额定电压。

8. 2. 4 辅助控制输出

固化在D25DAC上的控制输出的现场端子是0. 2英寸(5. 08mm)的紧缩式的接线板,适合#12AWG(4mm2 )导线和300VDC的额定电压。

8. 2. 5 供电

D25DAC的供电输入端子是一个有0. 2英寸间隔的紧缩式接线板,适于#12AWG(4mm2 )导线和300VDC的额定电压。

9.  标准和保护

在所有组合中,D25达到或超过以下要求:

IEC255-5绝缘/隔离:2500VRMS(3500VDC)>10Mohm,500VDC

IEC255-4脉冲/电压:5KV(1. 2/50μs)0. 5J

电力频率:250VRMS/500VRMS

IEC-255-22-1高频干扰:2. 5kV(1Mhz/400Hz)

IEC 801-4高速瞬变现象:4KV(2. 5Mhz/15ms/300ms)2KV(5. 0kHz/15ms/300ms)

IEEE C37. 90. 1-1989 SWC和高速瞬变现象:2. 5kV(1MHz/60Hz)5kV(10/150ns/60Hz)

IEC 801-5抗波动性:4kV(1. 2/50μs)2KA8/20μs)

IEC 1000-4-1环形波:4kV(100KHz)

IEC 801-2静电放电:8kv接触放电;15kV空气放电

IEC 801-3/IEEE C37. 90. 2-1987RFI/EMI灵敏度:10V/m(50kHz-1GHz)

IEC 电频磁场:100A/m(持续)1KA/m(1-3s)

IEC 100-4-10缓冲振荡磁场:100A/m(1mhz)

IEC 801-6传导干扰:9kHz-230MHz

CISPR 22ClassA,FCC Part 15 Class A辐射放射物

IEC 68-2-2干热:+70

IEC68-2-1冷:-40

IEC68-2-30湿热:+40℃,70%RH<=95%RH非冷凝

IEC68-2-6振动

IEC68-2-31下降和失衡

IEC 801 4,Level4;高速瞬变现象与所有I/O电缆夹耦合60s

EN 50081-2

EN 50082-2

10.  性能

当最大配置不超出以下标准时,D25的运行可达到最佳水平;

一个网络或两个以高速运行的SCADA规约

两个IED接口以高速运行

时钟输入运行

100ms内有128个事件的96个状态输入

1个周波内,两个脉冲累加器输入运行

50ms内,12个交流模拟输入改变(3个消失电压,9个过流)

5ms后一个控制输出;在另45ms后一个控制输出;在50ms后又一个控制输出

100ms55个模拟越限和故障报警

故障记录运行

模拟量事件报告运行

可编程算法扫描速率为2. 5MS(布尔型)