Solid insulated totally sealed switch cabinet OEM

12kv/24kv/35kv/38kv/40.5kv distribution network solid switchgear fully insulated and fully sealed watchdog demarcation switchgear switchgear NKVSR3  OEM/ODM

 

Recommended application areas

Low temperature and cold area : no SF6 gas application No need to consider the low temperature operation of SF6 gas It can also operate normally at -45 ° (SF6 insulation level drops at ultra-low temperature)

Plateau area: There is no need to consider the influence of plateau atmospheric pressure on insulation performance. (E.g. Xinjiang, Tibet, Qinghai, Gansu, Inner Mongolia, Yunnan, Guizhou, Sichuan)

Strong wind and sand areas : Dense-insulated ring main unit has a safety protection level of IP67. The control circuit room adopts special treatment to ensure long-term operation in strong sand areas. (For example, Inner Mongolia, Ningxia, Xinjiang, Qinghai, Tibet, Hebei, etc.)

Humid coastal area : epoxy sealed . Resistance to moisture Salt spray corrosion resistance Ensure that long-term use in coastal areas. (No heater is needed, not afraid of flooding) (e.g. Guangdong, Guangxi, Fujian, Zhejiang, Shanghai, Jiangsu)

Configurable mobile app measurement and control/smart SMS control/wireless control switch/remote remote control switch/national energy control/safety control/
GPRS/101/104/Background Intelligent Control/Intelligent Boundary Switch Box/Branch Box
DTU/FTU/RTU measurement and control intelligent switching station/user boundary floor box switch cabinet
 
The application of the distribution network watchdog demarcation switch on the 10kV 24kV 35kV 38kV line can greatly reduce the incidental power outage of the trouble-free line, reduce the scope of the fault outage, and shorten the user's power outage time, thereby improving the user's power supply reliability.

Boundary circuit breaker/load switch is a device that integrates the circuit breaker/load switch , the boundary protection measurement and control device , and the communication module. It can be configured with the distribution network, has small size and low investment. Its application can improve the performance of the distribution network. Safety and reliability are of great significance to ensure the safe operation of the power grid.
 

  

1. 
 The performance and main functions of the boundary load switch 1.1  Performance and structure The general boundary switch is composed of the switch body and the measurement and control unit. See the structure diagram 1.



 
           Figure 1 Schematic diagram of boundary switch controller
 
The main function of our company's demarcation switch is to automatically isolate the user-side phase-to-phase short-circuit fault during operation, automatically remove the user-side ground fault, and can be used to operate the load current.

The boundary load switch has a set of built-in voltage transformers and a set of built-in current transformers; it has a CPU internal processor and a communication module; it has voltage judgment and fault memory when a fault trips; it has a trip lock function.

Boundary load switch applies 10 kV 24kV 35kV 38kV  ungrounded, the arc suppression coil to ground via a low resistance grounding system or the distribution line of the user (including temporary user) boundary .

2.2 
 Main functions

2.2.1 
 Automatic removal of single-phase grounding faults When a single-phase grounding fault occurs on a user branch

, the boundary switch will automatically open to remove the faulty branch and ensure the safe operation of other branch users on the substation and feeder.

2.2.2  
Automatic isolation of phase-to-phase short-circuit faults When a phase-to-phase short-circuit fault occurs in the user branch line, the boundary load switch will immediately open the fault line after the substation outgoing protection trip. After the outlet switch of the substation is reclosed , the faulty line is isolated, so that other branch users on the feeder can quickly restore power. 2.2.3  Quickly locate the fault point, the user branch line fault causes the boundary switch





After the action, only the responsible user is powered off, and can take the initiative to report the fault information, so that the power company can quickly identify the accident point, timely deal with it on site, and restore the power supply to the faulty line as soon as possible.

2.2.4 
 Monitoring user load

boundary The load switch can transmit the detection data to the power management center to realize real-time monitoring of remote loads .

2.3  
Boundary load switch failure handling the

boundary load switch failure handling in Table 2.
Table 2 Fault handling method of boundary load switch
 

 

  System grounding method Fault point protection processing
Single-phase ground fault Neutral point unearthed system user boundary Trip immediately after being judged as permanent grounding
The neutral point is grounded through the arc suppression coil in the user's boundary
The neutral point is grounded via a small resistance in the user's boundary Trip before substation protection action
Neutral point ungrounded system outside the user boundary No action
The neutral point is grounded through the arc suppression coil outside the user's boundary
The neutral point is grounded through a small resistance outside the user's boundary
Phase-to-phase short circuit fault handling
 
In the user world
After the power-side circuit breaker trips, the boundary load switch opens
 
User out of bounds
No action

 

 

 Introduction to the body part of the solid fully insulated and fully sealed intelligent demarcation switchgear NK -12 /24/35

NKGT XGN15 -12/24/35 box-type fixed AC solid insulated metal-enclosed switchgear apparatus  

 

2 ) .1 Overview  

 NKGT XGN15 -12/24/35 box-type fixed AC solid insulated metal-enclosed switchgear apparatus

Referred to as " solid RMU ) is a highly reliable miniaturized maintenance switch cabinet ,

Products for three-phase AC 50 /60 Hz, voltage of 3-12 / 24/35 KV ring power supply system or radiation .

The solid insulated ring network cabinet NKGTXGN15 is a new generation of environmentally friendly composite insulated ring network cabinet. It is a fully sealed power supply unit, all live parts and switches are fully sealed in an epoxy resin shell, and there is no SF6 gas in the shell The entire switchgear is not affected by the external environment, ensuring operational reliability and personal safety, and achieving maintenance-free. 

The solid insulated ring main unit is composed of three types of switches, namely V unit (circuit breaker unit), unit (load switch unit). unit (combined electrical unit), each unit can be used alone or freely expanded, and its structure is divided into The instrument room, operating mechanism and primary part are intelligently controlled. The instrument room can be equipped with microcomputer protection (controller). The primary part adopts APG automatic gel process, and the isolating switch and arc extinguishing chamber are completely sealed in epoxy resin, and there are special The connector is connected to the bus bar. The arc extinguishing chamber adopts special copper-chromium contact material, -type longitudinal magnetic field contact, and a complete one-time sealing process The interrupting short-circuit current capability and stability, electrical life, temperature rise and insulation level of the isolated chamber are all higher than before The isolated isolation chamber (copper-aluminum contact material), the cup-shaped longitudinal magnetic field contact structure, and the incomplete one-time sealing process have been significantly improved. The operating mechanism adopts an integrated spring operating mechanism that cooperates with the switch, that is, the isolation switch and the main switch spring operating mechanism are integrated, which can facilitate interlocking, and has fewer mechanical parts, reduces unnecessary transmission links, and has high reliability. Electric operation can be realized according to user needs.

Solid insulation fully enclosed switchgear: it uses solid insulation material as the main insulation medium and conductive connection, isolation switch, grounding switch, main bus bar, branch bus bar and other main conductive loops, single or combined, and then covered and packaged with solid insulation medium into one or more A fully insulated and fully sealed module with certain functions that can be combined or expanded again .

The ring network unit is suitable for 3~ 12KV/24KV/35KV 50Hz/60Hz three-phase AC power distribution system, used for ring network power supply or terminal power supply. The ring network unit can be installed in the power distribution system of industrial and mining enterprises, residential communities, schools, parks, etc., and can also be installed in compact box-type substations for the control and protection of distribution transformers. Therefore, both indoor and outdoor ring network units realize power distribution automation.

   This series of ring network cabinets conform to

IEC62271-1-2007 "High Voltage Switchgear and Control Equipment Part 1: General Specification"

IEC620071-200-2003 1~52KV AC Metal-enclosed Switchgear and Control Equipment"

GB3906-2006 3.6~40.5KV AC Metal-enclosed Switchgear and Control Equipment"

GB/T11022-2011 "Common technical conditions for high-voltage switchgear and control equipment standards"

GB1984-2014 "High Voltage AC Circuit Breaker"

GB1985-2014 "High Voltage AC Isolating Switch and Grounding Switch"

GB3804-2004 3.6KV~40.5KV High Voltage AC Load Switch"

DL/T404-2007 3.6KV~40.5KV AC metal enclosed switchgear and control equipment"

DL/T593-2016 "Common technical conditions for high-voltage switchgear and control equipment standards"

Q/GDW730-2012 12KV solid insulated ring main unit technical conditions"

 DL/T402-2016 "High Voltage AC Circuit Breaker" standard ,

 

Product code of manufacturer

NKGT(XGN-12)

NKGT产品企业代号

                      X箱型 Cubicle Type
                             G固定式 Fixde Type
                                 N户内 Indoor
                                   口设计序号 Design Series
                                        12/24/35额定电压kV Rated Voltage
                                               口组合方案(V、F、C、D)  
                                                      Combination Scheme
                                                      V: 真空断路器单元
                                                      V: VCB unit
                                                       F: 负荷开关熔断器组合单元
                                                       F : LBS-Fuse combination unit
                                                       C: 负荷开关单元
                                                       C: LBS unit
                                                       D: 直接进出线单元

 

                                                       D: in & Out Directly unit
 

Normal service conditions

Ambient temperature: highest + 60, lowest in - 40

Environmental humidity: average daily do not more than  95%, average monthly do not more than 90%

Altitude :Not more than 1000 meters

Seismic intensity : Not more than 8 degrees

No fire and explosion danger, no chemical corrosion and violent vibration places

 

 

序号

RF

环网柜主要技术参数                                         

名称 Parameter

单位

Unit

参数Value

 

 

 

C mod

F mod

Vmod

D  mod

1

额定电压 Rated voltage

KV

12

2

额定

绝缘水平

Rated insulating level

工频耐压(1min)

Power Frequency withstand voltage(1min.)

相间,相对地

Between phase,phase to earth

KV

42

42

42

42

3

 

 

断口Across the opened break

KV

48

48

48

48

4

 

雷电冲击耐压(峰值)

LightningWithstand Voltage(peak)

相间,相对地

Between phase,phase to earth

KV

75

75

75

75

5

 

 

断口 Across the opened break

KV

85

85

85

85

6

额定频率 Rated frequency

Hz

50

7

额定电流 Rated current

A

630

125

630

630

8

额定转移电流 Rated transfer current

A

 

3700

 

 

9

额定短路开断电流 Rated short circuit breaking current

KA

 

31.5

25

 

10

额定短路关合电流 Rated making current (E2)

KA

50(3次)

50

50

 

11

额定短时耐受电流(负荷/接地开关)

 Rated shortime withstand current (LBS/ES)

KA

25

25

25

25

12

额定短路持续时间(负荷/接地开关)

Rated short circuit duration (LBS/ES)

s

4

4

4

4

13

额定峰值耐受电流(负荷/接地开关)

Rated peak withstand current(LBS/ES)

KA

50

50

50

50

14

额定短路关合电流 (接地开关)Rated making current(ES)

KA

50

 

15

额定机械寿命(负荷开关)Rated mechanincal life(LBS)

times

3000

10000(VCB)

(断路器)

16

额定机械寿命(接地开关)Rated mechanincal life(ES)

times

3000

 

17

额定

开断电流

Rated breaking current

闭环开断电流Breaking current of close loop

A

630

 

 

 

 

 

有功负载开断电流

Breaking current of active power

A

630

 

 

 

 

 

电缆充电开断电流

Breaking current of cable charging

A

10

 

 

 

18

触头   Contact opening distance

mm

9±1

 

9±1

 

19

超行程     Overtravel

mm

3.0 ±0.5

 

3.0 ±0.5

 

21

相间中心距Center distance between phases

mm

130±1.5

 

130±1.5

 

22

主回路电阻Main circuit resistance (不含熔断器)

μΩ

350

750

350

 

23

合闸时间   Closing time

ms

10000

 

25-60

 

24

分闸时间   Opening time

ms

17-45

 

17-45

 

25

平均合闸速度

m/s

 

 

0.0.2

 

26

平均分闸速度

m/s

1.3±0.2

 

1.3±0.2

 

27

三相不同期性

ms

2

 

2

 

28

二次回路1min工频耐压

Power frequency withstand voltage on secondary circuit(1 min.)

KV

2

29

负荷开关短路关合电流操作循环次数

Operation cycle times for short circuit making current of LBS

times

3(E2) 3(E2 class)

30

局部放电Partial discharge

PC

20(1.2Ur下测量)               

measured at 1.2ur

31

柜体防护等级

Protetcion class of cubicle body

 

IP4X

 

柜体及外壳防护等级

Protetcion class of  the shell

 

IP67

 

 

 

序号

RF

环网柜主要技术参数                                         

名称 Parameter

单位

Unit

参数Value

 

 

 

C mod

F mod

Vmod

D  mod

1

额定电压 Rated voltage

KV

24

2

额定

绝缘水平

Rated insulating level

工频耐压(1min)

Power Frequency withstand voltage(1min.)

相间,相对地

Between phase,phase to earth

KV

64

64

64

64

3

 

 

断口Across the opened break

KV

79

79

79

79

4

 

雷电冲击耐压(峰值)

LightningWithstand voltage(peak)

相间,相对地

Between phase,phase to earth

KV

125

125

125

125

5

 

 

断口

Across the opened break

KV

145

145

145

145

6

额定频率 Rated frequency

Hz

50

7

额定电流 Rated current

A

630

125

630

630

8

额定转移电流 Rated transfer current

A

 

3700

 

 

9

额定短路开断电流 Rated short circuit breaking current

KA

 

31.5

25

 

10

额定短路关合电流 Rated making current (E2)

KA

50(3次)

50

50

 

11

额定短时耐受电流(负荷/接地开关)

 Rated shortime withstand current (LBS/ES)

KA

25

25

25

25

12

额定短路持续时间(负荷/接地开关)

Rated short circuit duration (LBS/ES)

s

4

4

4

4

13

额定峰值耐受电流(负荷/接地开关)

Rated peak withstand current(LBS/ES)

KA

50

50

50

50

14

额定短路关合电流 (接地开关)Rated making current(ES)

KA

50

 

15

额定机械寿命(负荷开关)Rated mechanincal life(LBS)

times

3000

10000(VCB)

(断路器)

16

额定机械寿命(接地开关)Rated mechanincal life(ES)

times

3000

 

17

额定

开断电流

Rated breaking current

闭环开断电流Breaking current of close loop

A

630

 

 

 

 

 

有功负载开断电流

Breaking current of active power

A

630

 

 

 

 

 

电缆充电开断电流

Breaking current of cable charging

A

10

 

 

 

18

触头   Contact opening distance

mm

12±1

 

12±1

 

19

超行程     Overtravel

mm

3.0 ±1

 

3.0 ±1

 

21

相间中心距Center distance between phases

mm

380±1.5

 

380±1.5

 

22

主回路电阻Main circuit resistance

μΩ

350

750

(不含熔断器)

350

 

23

合闸时间   Closing time

ms

10000

 

25-80

 

24

分闸时间   Opening time

ms

23-50

 

23-50

 

25

平均合闸速度

m/s

 

 

0.5~0.9

 

26

平均分闸速度

m/s

1.1~1.7

 

1.1~1.7

 

27

三相不同期性

ms

2

 

2

 

28

二次回路1min工频耐压

Power frequency withstand voltage on secondary circuit(1 min.)

KV

2

29

负荷开关短路关合电流操作循环次数

Operation cycle times for short circuit making current of LBS

times

3(E2) 3(E2 class)

30

局部放电Partial discharge

PC

20(1.2Ur下测量)               

measured at 1.2ur

31

柜体防护等级

Protetcion class of cubicle body

 

IP4X

 

柜体及外壳防护等级

Protetcion class of  the shell

 

IP67

 

 

 

序号

RF

环网柜主要技术参数                                         

名称 Parameter

单位

Unit

参数Value

 

 

 

C mod

F mod

Vmod

D  mod

1

额定电压 Rated voltage

KV

35

2

额定

绝缘水平

Rated insulating level

工频耐压(1min)

 Power frequency withstand voltage(1min.)

相间,相对地

Between phase,phase to earth

KV

95

95

95

95

3

 

 

断口Across the opened break

KV

110

110

110

110

4

 

雷电冲击耐压(峰值)

lightningWithstand voltage(peak)

相间,相对地

Between phase,phase to earth

KV

185

185

185

185

5

 

 

断口

Across the opened break

KV

215

215

215

215

6

额定频率 Rated frequency

Hz

50

7

额定电流 Rated current

A

630

125

630

630

8

额定转移电流 Rated transfer current

A

 

3700

 

 

9

额定短路开断电流 Rated short circuit breaking current

KA

 

31.5

25

 

10

额定短路关合电流 Rated making current (E2)

KA

50(3次)

50

50

 

11

额定短时耐受电流(负荷/接地开关)

 Rated shortime withstand current (LBS/ES)

KA

25

25

25

25

12

额定短路持续时间(负荷/接地开关)

Rated short circuit duration (LBS/ES)

s

4

4

4

4

13

额定峰值耐受电流(负荷/接地开关)

Rated peak withstand current(LBS/ES)

KA

50

50

50

50

14

额定短路关合电流 (接地开关)Rated making current(ES)

KA

50

 

15

额定机械寿命(负荷开关)Rated mechanincal life(LBS)

times

3000

10000(VCB)

(断路器)

16

额定机械寿命(接地开关)Rated mechanincal life(ES)

times

3000

 

17

额定

开断电流

Rated breaking current

闭环开断电流Breaking current of close loop

A

630

 

 

 

 

 

有功负载开断电流

Breaking current of active power

A

630

 

 

 

 

 

电缆充电开断电流

Breaking current of cable charging

A

10

 

 

 

18

触头   Contact opening distance

mm

22±1

 

22±1

 

19

超行程     Overtravel

mm

5 ±1

 

5 ±1

 

21

相间中心距Center distance between phases

mm

710±1.5

 

710±1.5

 

22

主回路电阻Main circuit resistance

μΩ

350

750

(不含熔断器)

350

 

23

合闸时间   Closing time

ms

10000

 

145

 

24

分闸时间   Opening time

ms

70

 

70

 

25

平均合闸速度

m/s

 

 

0.7±0.2

 

26

平均分闸速度

m/s

1.5±0.2

 

1.5±0.2

 

27

三相不同期性

ms

2

 

2

 

28

二次回路1min工频耐压

Power frequency withstand voltage on secondary circuit(1 min.)

KV

2

29

负荷开关短路关合电流操作循环次数

Operation cycle times for short circuit making current of LBS

times

3(E2) 3(E2 class)

30

局部放电Partial discharge

PC

20(1.2Ur下测量)               

measured at 1.2ur

31

柜体防护等级

Protetcion class of cubicle body

 

IP4X

 

柜体及外壳防护等级

Protetcion class of  the shell

 

IP67

 
 

 

变压器初级电压Transformer primary Voltage (kV)

 

变压器额定容量(KVARated capacity of transformer (kVA)

 

25

50

75

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

3

熔断器

额定电流Fuse rated current

A)

16

20

31.5

40

50

50

63

80

100

125

160

 

 

 

 

 

3.3

10

20

25

40

40

40

63

80

80

125

125

160

 

 

 

 

6

6

16

20

25

25

31.5

40

50

50

63

80

100

125

160

 

 

10

6

10

10

16

20

25

25

31.5

40

50

50

63

80

100

125

 

11

6

10

10

16

20

20

25

25

40

40

50

50

63

80

100

125

 

Safety and protection

In front of the disconnector visual fracture cabinet, there is an obvious isolation fracture visual window, which can view the isolation closing position, isolation opening position and grounding closing position. It is very convenient.

Pressure relief design internal arc pressure valve: when there is arcing in the product, the pressure will be released from the pressure relief valve. The arc will be discharged to the cable trench to avoid accidental injury to operators.

The green design does not use SF6 gas as arc extinguishing medium and insulation. It has no pollution to the environment. The primary circuit adopts less contact design to ensure low energy consumption during operation.

 

application area

Low temperature and cold area: there is no SF6 gas application. It does not need to consider the low temperature operation of SF6 gas. It can also operate normally at - 45 ° C.

Plateau area: no need to consider the influence of Plateau Atmospheric Pressure on insulation performance.

Strong wind and sand area: dense insulation ring main unit body safety protection grade is IP67. Special treatment is adopted in control circuit room to ensure long-term operation in strong wind and sand area.

Coastal humid area: epoxy resin sealing, moisture resistance, salt spray corrosion resistance, to ensure long-term use in coastal areas.

Areas with high environmental protection requirements: the impact of SF6 gas on atmospheric warming has been highly valued, and SF6 gas has been cancelled in solid ring main unit, which has no pollution and damage to the environment and human body.

In the smart grid: since the main switch can be electrically operated, the intelligent controller developed by our company can be used for remote control, telemetry and remote signaling of the switchgear and substation site. It can not only carry out decentralized control, but also facilitate centralized control.

 

 

固体绝缘环网柜机芯结构特点  Structural characteristics of solid insulated ring main unit

 

Vacuum circuit breaker has the ability of breaking short-circuit current. It is used for overload and short-circuit protection of circuit and electrical equipment. It has the advantages of small volume, light weight, small maintenance workload, fire prevention, explosion-proof and low operation noise. It is an ideal circuit breaker to replace oil circuit breaker and SF6 circuit breaker. It is widely used in power, metallurgy, communication, etc High frequency heating and other distribution systems in the industry. Vacuum interrupter for circuit breaker is the key component of vacuum circuit breaker and the heart of vacuum circuit breaker. It basically determines the main performance of circuit breaker.

Solid insulation system

The current carrying conductors, such as vacuum interrupter and upper and lower outlet sockets, are packaged as a whole by the solid sealing pole formed by APG process. The disconnector is installed in the cavity of the fixed pole, so that the phase to phase insulation is mainly solid insulation. Single phase insulated bus design can avoid serious faults such as phase to phase and ground. Bus expandable design. Realize unlimited expansion of function unit.

Three position knife switch

All switch cabinets are equipped with three position knife switch. The three position knife switch and the main switch are built into the fixed pole. Three phase linkage. It can be operated to realize three positions of work / isolation / grounding. Mechanical interlock is adopted with the main switch. Only when the main switch is in the opening position, the three position knife switch can act.

 

Operating mechanism

The operating mechanism of the circuit breaker is a spring operating mechanism. It has the characteristics of simple structure, reliable action, small size and maintenance free. The closing power can be adjusted up and down according to the user's requirements. The mechanism can be manually stored energy, manually closed and manually opened. It can also be electric energy storage and electric opening and closing, which is convenient for users to operate.

The operating mechanism of three position knife switch adopts the design of through spring. It can quickly open and close. It has the function of breaking and closing certain load current. Besides manual operation, it can also carry out electric operation. It can realize intelligent remote control isolation and grounding, which greatly facilitates the use of users.

 

Solid insulated ring main unit is a kind of small switch cabinet, its structure is as follows:

A. High voltage load switch and high voltage live parts are sealed in epoxy resin insulating sleeve without any gas. The vacuum interrupter is small in size and reliable in arc extinguishing. The load switch is equipped with grounding switch. It has three positions of closing, opening and grounding. The grounding knife has the function of isolating knife.

B. It can be combined at will. Each unit is led out through three high voltage bushing, so the cable connection is convenient.

C. The imported sealing box is adopted, and strict sealing measures are adopted at the connection of operating mechanism and high-voltage bushing, and the performance is good.

D High voltage bushing and high-voltage insulating cylinder made of imported epoxy resin are adopted in APG process. The insulating cylinder and high-voltage bushing are assembled with silicone rubber sleeve and have good sealing effect.

 

 Each channel is equipped with independent operating mechanism. The mechanism is installed on the front of the cabinet body and has a variety of mechanical interlocking functions.

F Load switch and grounding switch are equipped with spring operating mechanism. Load switch can be operated manually or electrically. Grounding switch not only has grounding function, but also has isolation function. It can only be operated manually.

G. the circuit breaker can be equipped with permanent magnet operating mechanism. It can be electrically closed and opened. It can be opened manually, but it can not be closed manually. The circuit breaker can also be equipped with spring mechanism, which can be manual or electric. The interface of distribution automation is reserved.

H. There is a visual window on the panel of the ring main unit, which can directly observe the opening and closing state of the disconnector fracture, and there are obvious breaking points.

 each RMU unit is composed of three separate insulating cylinders in parallel. It is easy to install and replace. The biggest advantage is to avoid phase to phase discharge.

J. the main components of solid insulation fully enclosed ring main unit are composed of insulating cylinder and vacuum interrupter.

 The solid insulation material is imported epoxy resin. The thickness is not less than 10 mm. It has strong corrosion resistance and high insulation capacity. The internal space is more than 150 mm. The phases are separated separately and connected together through the base plate mounting frame. The combination is flexible, the structure is simple, reasonable and beautiful.

L. There is no fastener on the surface of the box for disassembly. It has good anti-theft property. The box has the protection grade of ip33 and good rain proof performance.

M  The top cover is equipped with ventilation . The air inlet is located at the lower part of the box body, and dust-proof filter screen is set. The air outlet is set at the top of the box and hidden under the room slot to form air convection from bottom to top. The box has good heat insulation and ventilation effect. The cover is provided with a certain angle of drainage angle.

N. The box has a sealed floor with cable inlet to prevent moisture in the cable trench from entering the box.

O the door is sealed with sealing strip. The door lock is rainproof structure, and the limited pull rod makes the door easy to fix when the door is opened.

 The switch in box is of solid insulation and fully sealed structure. There is no need for heater. The cable head can be divided into touch type and non touch type according to the user's requirements. It is not afraid of immersion.

 

Operating mechanism and operation

A. each load switch and grounding switch in the ring network unit are equipped with independent spring operating mechanism. They are installed on the front panel of the cabinet, and can be operated manually make. There are two operation holes on the panel for operating load switch and grounding switch respectively. Vacuum circuit breaker is equipped with integrated permanent magnet operating mechanism and spring operating mechanism.

 

B. operating instructions of load switch power transmission operation

First close the isolating grounding switch: insert the operating handle into the grounding operation hole (when the disconnector is in the grounding closing state) · rotate counterclockwise to open the grounding

Then insert the operating handle into the isolation operation hole. Turn it anticlockwise to close the isolating knife.

Re closing the load switch: insert the operating handle into the operation hole of the main switch. Turn it about 2 times anticlockwise to close the main switch.

Blackout operation

First open load switch: turn the opening knob anticlockwise to open the switch.

Then open the isolation grounding switch: insert the operating handle into the operating hole of the isolation mechanism. Rotate it clockwise to separate the isolating knife, and then insert the operating handle into the grounding operation

Inside the hole. Rotate clockwise. Close the grounding.

C operating instructions of circuit breaker

D mechanical interlocking: there is mechanical interlocking between load switch, circuit breaker and grounding switch. When the load switch and circuit breaker are in the closing state, the grounding switch cannot be opened

Closing: grounding switch is in closing state, load switch and circuit breaker cannot be opened or closed.

E. Installation and replacement of fuses

(1) Close the grounding switch first.

(2) Lift the handle and rotate it anticlockwise to make the pin out of the groove

(3) Install the striker mechanism into the fuse barrel, make the pin in the slot, rotate clockwise, make the operation handle parallel to the panel, and then press down the handle with force.

(4) It can only be opened when the load switch is grounded.

 

结构示意图 Structure diagram

 

 

 

 

 

产品外观展示Product appearance display

户内型环网单元的柜体结构如图示 The cabinet structure of indoor ring network unit is shown in the figure

 

 

户外型环网单元的柜体结构如图示The cabinet structure of outdoor ring network unit is shown in the figure

  

 

 

 

 

 安装及尺寸图Installation

●开关设备安装基础的施工应符合《电力建设施工及验收技术规范》中的有关条款规定

The foundation for cubicle should be in conformance with relative requirements stipulated inThe code of erection and

acceptance of electric power construction

●柜体单列时,柜前走廊以1.5米为宜:双列布置时,柜间操作通道走廊以2米为宜

The corridor width in front of cubicles arranged in one row takes l.5m properly, and 2m proper for double rows arrangement

●一次电缆终端安装严格按相关工艺要求

The fitting of primary cable teerminals should be strictly according to relevant technology requirements

●电缆沟上方预埋10号槽钢,柜子放在槽钢上固定

The No. 10 U steels built in the top edges of cable trench can be used as the base of cubicle

环网单元应安装在通风良好的地方.在正面操作和维护.环网单元的底座有地脚安装孔.在室内柜体可以离墙或 靠墙安装.安装位置如图示。安装地基上所铺设轨道的平面度.每平米范围不得超过2mm 环网单元的底座必须固 定在地基上。户外安装时地基要求建在较高地势处.四周离墙或遮挡物的距离不得小于1.以免妨碍开门。坑壁用 水泥和实心砖砌制.表面作防渗水处理。坑壁及基础平台用12.5水泥沙浆面厚度为20mm.表面要平整。混泥土制 做按GB232-82《电气装置安装工程施工及验收规范》。电缆安装完成后.电缆室底板应进行密封处理.防止地沟潮气进入。环网单元的接地必须与现场的接地网相连。环网单元的接地处有接地标志。

The ring network unit shall be installed in a well ventilated place. It shall be operated and maintained in the front. The base of the ring network unit has anchor mounting holes. In the indoor cabinet, it can be installed away from or against the wall. The installation position is shown in the figure. The flatness of track laid on the installation foundation shall not exceed 2mm per square meter. The base of ring network unit must be fixed on the foundation. When installing outdoors, the foundation is required to be built at a higher terrain. The distance from the wall or shelter should not be less than 1 meter to avoid obstructing the door opening.

The pit wall is made of cement and solid brick, and the surface is treated with anti seepage. The thickness of 1:2.5 cement mortar for pit wall and foundation platform is 20 mm, and the surface shall be smooth. The concrete shall be made according to gb232-82 code for construction and acceptance of electrical installation engineering. After cable installation, the bottom plate of cable room shall be sealed to prevent moisture from entering trench. The grounding of ring network unit must be connected with the grounding grid on site. There are grounding marks at the grounding point of ring network unit.

 

 

订货时需确定的资料内容  The data needed for order

●一次线路系统图,排列图及平面布置图

Primary schame and the layout or the arrangement sketch.

●二次线路原理图,其中包括操作、信号、保护回路各电器元件的型号规格

Principle diagram of secondary circuit, including the type and the spec of electric components in operation, signal and

protection circuit.

●开关柜内电器元件的型号、规格、数量

The type, specification and quantity of primary components in the cubicle

●特殊环境条件下的要求

Special ambient condition

●附件及备件的种类和数量

The sorts and the quantity of accessories and spare parts.

●用户需要的特殊要求,订货时可以与制造厂协商

For special requirement, if any, please contact the  manufacturer

 

 

 

 

 

 

地基图Foundation 

 

 

说明:

1.基础施工上表面要水平,坑口边沿要预埋10#槽钢,预埋底架与混凝土面平或高出 1-2mm

2.需在电缆井旁边开一入口,以便人能进入电缆井.便于电缆安装。

3 L.S.H分别为户外箱长宽高

 

Explain:

1The upper surface of foundation construction shall be horizontal,

10 × 10 channel steel shall be embedded at the edge of the pit,

The embedded underframe shall be level or 1-2mm higher than the concrete surface

2. It is necessary to open an entrance beside the cable well, so that people can enter the cable well and facilitate cable installation.

3 L  S H  is the outdoor box   length, width and height respectively

 

 

 

运输和储存

包装好的环网单元可用电动叉车或吊车搬运,环网单元上配备了吊环.供搬运时吊装之用。吊运用绳索不能短于2m。 环网单元在使用现场安装前应放在干燥、通风、无灰尘的地方。如用塑料袋覆盖.底部应敞开通风。

 

使用与维护

使用前的检查:环网单元在使用前.为了人身及设备安全.必须进行下列检查

-检查主电路和接地电路是否正确连接。

-检查机械联锁是否正确、可靠。

•检查环网单元内负荷开关和接地开关的操作是否灵活、正确。

•检査高压电缆的连接是否正确、可靠。

B .运行

•应按规定的操作顺序.使环网单元投入运行。

C.维护:本设备基于如下优点.不需要进行日常维护

•所有的带电部件均安装在环氧塑脂绝缘筒内。

•所有置于环氧塑脂绝缘筒外面的操作机构部件都已经进行了电镀处理。

•主轴用铜轴套支撑,就是不加润滑剂,也可以连续、有效地工作。

注意:若环网单元有故障.不要试图用钻孔机、切割机或其它工具打开环网单元修理.这些操作只能有本公司人员 负责。

 

随机文件和附件

产品出厂时.随机提供以下资料和附件:

•产品安装使用说明书。-产品岀厂试验报吿。•产品合格书。•装箱清单。-操作手柄。-其他附件。

 

Transportation and storage

The packaged ring network unit can be transported by electric forklift or crane. The ring network unit is equipped with lifting rings for lifting during transportation. The rope used for hoisting shall not be shorter than 2m. The ring network unit should be placed in a dry, ventilated and dust-free place before installation on site. If covered with plastic bags, the bottom should be open and ventilated.

Use and maintenance

A pre use inspection: before using the unit, the following inspections must be carried out for personal and equipment safety

-Check that the main circuit and the ground circuit are properly connected.

-Check whether the mechanical interlock is correct and reliable.

-Check whether the operation of load switch and grounding switch in ring network unit is flexible and correct.

-Check whether the connection of high voltage cable is correct and reliable.

 

B. Operation  The ring network unit shall be put into operation according to the specified operation sequence.

C. Maintenance: the equipment is based on the following advantages. No routine maintenance is required

All live parts are installed in epoxy resin insulated cylinder.

All operating mechanism components outside the epoxy resin insulated cylinder have been electroplated.

The main shaft is supported by copper shaft sleeve, which can work continuously and effectively without lubricant.

Note: if there is a fault in the ring network unit, do not attempt to open the ring network unit for repair with drilling machine, cutting machine or other tools. These operations can only be carried out by our company's personnel.

 

Attached documents and attachments

When the product leaves the factory, the following data and accessories shall be provided with the machine:

Product installation and operation manual. -Test report of product delivery. Product qualification certificate. 

packing list. -Operating handle. -Other attachments.