NK3S-12KV permanent magnetic vacuum breaker

 NK3S-12kv  intelligent permanent magnet three-phase synchronous closing circuit breaker] Split-phase control intelligent permanent magnet circuit breaker

(one permanent magnet operating mechanism per phase)

My company's permanent circuit breaker due to the very few moving parts, eliminating complex mechanical lock and release system, which has irreplaceable advantages: less failure, reliable, long life (up to million or more times), without lubrication At present, it has extensive power supply, coal mines, steel making, railways, etc.

   The YCK380 series permanent magnet switch controller independently developed by our company , together with our permanent magnet operating mechanism, can realize the opening and closing operation of the circuit breaker, the over-current breaking protection, the watchdog protection, the wireless remote control operation, and the coincidence. The gate operation, as well as the distribution network automation function, make the switch a maintenance-free intelligent circuit breaker.

 

 

People-oriented, quality win is the company's business philosophy, leading technology, customer service for business purposes, highly value product quality, professional and enterprising, tenacious, teamwork as the spirit of enterprise. The company will always be market-oriented, focus on customer needs, strive to forge ahead, strive to develop and produce more and better high-tech products, and serve the customers.

 

 

 

 

1.        NK3S intelligent permanent magnet circuit breaker product overview  -- three phase independent permanent magnet mechanism drive   Split phase control intelligent permanent magnet breaker

 

 

 

 

 

1.1 main use

 

NK3S  type outdoor high permanent magnetic vacuum circuit breaker (hereinafter referred to as breaker) is the highest rated voltage 12 is / 24kV / 35kV / 38kV 50Hz three-phase AC power distribution equipment outdoors. It is mainly used for breaking and closing the load current, overload current and short-circuit current in the power system. It is suitable for protection and control in power distribution systems of substations and industrial and mining enterprises. It is more suitable for rural power grids and frequently operated places, especially for the needs of urban network and rural network transformation.

This installation and installation manual specifies the main technical parameters of the circuit breaker, the product structure, and the principles and methods of operation, installation, use and maintenance.

1.2 reference standard

GB1984-2003    "AC high voltage circuit breaker"

GB/T11022-1999  "Common technical requirements for high-voltage switchgear and control equipment standards"

GB311.1-1997    "Insulation coordination of high voltage power transmission and transformation equipment: high voltage test technology"

GB3309-1989    "Mechanical test of high voltage switchgear at room temperature"

DL/T403-2000  Technical Conditions for Ordering 12~40.5kV High Voltage Vacuum Circuit Breaker"

1.3 Environmental conditions used

1.3.1 The altitude does not exceed 2000 meters;

1.3.2 Ambient air temperature: -45 °C ~ +40 °C ;

1.3.3 wind speed is not more than 35m / s ;

1.3.4 pollution class: IV grade

1.3.5 Installation place: no flammable, explosion hazard, chemical corrosion.

1.3.6 The earthquake intensity does not exceed degrees

 

 

 

 

 1.4 main features

 

 

1.4.1 Fully sealed structure: good sealing performance, help to improve moisture and anti-condensation performance, adapt to high temperature and humidity, and effectively avoid mechanical corrosion caused by long-term outdoor environment.

1.4.2 The circuit breaker adopts a three-phase strut structure, which has stable and reliable breaking performance, compact and reasonable overall structure, small volume and light weight. Long service life and other characteristics.

1.4.3 Vacuum interrupter: The breaking performance is stable and reliable, the contact wear is small, there is no danger of flammability and explosion, and safety can be maintenance-free.

1.4.4 Three-phase props and current transformers are made of high-quality outdoor silicone rubber solid insulation, which is resistant to high, low temperature, UV and aging.

1.4.5 breaker operating mechanism with permanent magnet, fewer parts, small size, maintenance-free, mechanical life of or more million times. The operating mechanism is placed in a sealed housing to solve the problem of corrosion of the mechanism and improve the reliability and service life of the mechanism.

1.4.6 The opening and closing operation of the circuit breaker can be performed by manual and electric splitting and closing operations and providing a remote operation interface. It can be integrated with the controller to realize distribution automation, and can be combined with the demarcation controller to form a watchdog demarcation circuit breaker or recloser .

1.4.7 The ABC phase of the circuit breaker is equipped with a current transformer, and is equipped with an outdoor voltage transformer for automatic over-current protection of the over-current and supporting information analysis with the intelligent controller to realize various protection functions.

 

 

 

 

1. 5 product model

 

NK3S-12G 630A/1250A - 20/31.5

20/31.5 rated short circuit breaking current ( kA )

630/1250 rated current ( )

isolation switch

12/24/35kV/38kV  maximum working voltage ( kV )

NK3S  design serial number three-phase independent permanent magnet mechanism drive  

2. Technical parameters

2.1 The main technical parameters are shown in Table 1.

2.2 Mechanical characteristics are shown in Table 2.

2.3 Operating mechanism characteristics are shown in Table 3.

2.4 The size and installation dimensions of the circuit breaker are shown in Figure Figure , Figure , and Figure . 

3. Operating mechanism and its operating principle

3.1 manual mechanism action principle .

  Table main technical parameters of the circuit breaker

Serial number

Term     project

unit

Number of  values

1

Rated voltage

kV

12

2

Rated frequency

Hz

50

3

Rated current

A

630/(1250)

4

Rated short-circuit breaking current

kA

20/(31.5)

5

Rated peak withstand current ( peak )

kA

50/(80)

6

Rated short circuit withstand current / duration

kA/s

20/4 / (31.5/4)

7

Rated short circuit closing current (peak )

kA

80

8

Rated operation sequence

 

Minutes -0.3s - combined points - 180s - combined points

9

Mechanical life

Times

10000

10

Rated current breaking times

Times

10000

11

Rated short-circuit breaking current breaking times

Times

30

 

12

Power frequency withstand voltage (1min):

wet ) phase to ground

dry ) phase, ground / fracture

 

kV

 

34

42/49

13

Lightning impulse withstand voltage (peak) phase to ground, ground /fracture

kV

75/85

14

Secondary circuit 1min power frequency withstand voltage

V

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table main mechanical characteristics of the circuit breaker

 

 

 

 

Serial number

parameter name

unit

data

1

Contact opening distance

Mm

11±1

2

Contact overtravel

Mm

3±0.5

3

Average closing speed

m/s

0.6±0.2

4

Average opening speed

m/s

1.0~1.4

5

Contact closing bounce time

Ms

≤2

6

Interphase center distance

Mm

280±2

7

Three-phase switching

Ms

≤2

8

Conductive loop resistance of each phase

μ Ω

≤80

9

Closing time

Ms

30~50

10

Opening time

Ms

30~70

 

 

 

 

 

 

 

 

3.1.1 Working principle :

When the switch is closed, the controller controls the external circuit to supply the drive current to the coil. The magnetic field generated by the coil current is in the same direction as the magnetic field generated by the permanent magnet, and is superimposed on each other. As the coil drive current increases, the drive force generated by the magnetic field gradually changes. Large, when the driving force is greater than the opening holding force provided by the circuit breaker, the moving iron core follows Newton's law: F=ma moves downward, and the driving force increases sharply as the magnetic gap decreases, eventually pushing the moving iron core to Closing position.

At this time, the controller cuts off the coil power supply according to the protection time set by the program. Since the ferromagnetic circuit has been closed at this time, the magnetic force of the permanent magnet has satisfied the closing force of the circuit breaker, so that the circuit breaker is in the closed state.

When opening, a small current is applied to the coil, and the magnetic field generated by the current is opposite to the direction of the magnetic field generated by the permanent magnet, which weakens the magnetic field of the ferromagnetic circuit. When the magnetic force is smaller than the closing holding force of the circuit breaker, the combined force pushing mechanism of the circuit breaker The moving iron core moves in the direction of opening and completes the opening process.

The switch adopts the synchronous closing technology to realize the synchronous closing of the circuit breaker effectively suppressing the operation overvoltage and the inrush current  .

Particularly suitable for capacitor operation

 

 

 

3.3 wiring diagram

 

4. Isolation switch optional )

4.1 For users who need to install isolation switch NK3S-12G series switch can be used . The external dimensions and structure are shown in Figure 1 and Figure 2. The isolating switch is bolted to the mechanism box of the NK3S-12 circuit breaker. It is rugged, stable, easy to disassemble and reliable, and can be flexibly installed.

4.2 The main technical parameters of the isolating switch are shown in Table 3.

 

Serial number

Term       project

unit

parameter

1

Rated voltage      

kV

12

2

Rated current

A

630/1250

3

4s rated short-time withstand current (RMS)

kA

16 20/31.5

4

Rated peak withstand current

40 50/80

5

1min power frequency withstand voltage

Ground, phase

kV

42

Fracture

48

6

Loop resistance (breaker wiring board to isolation switch between the board)

μΩ

≤100

7

Center yaw amount when three-phase knife shutter is closed

Mm

≤2

8

Three-phase knife gate division and closing synchronization deviation

≤2

9

Conductive part to ground insulation distance

≥160

10

Fracture opening

≥200

11

weight

Kg

≤40

4.3 isolation switch structure features

The isolating switch is composed of an isolating frame 12 , an insulator , an insulating rod 11 , a blade 10 , an isolating main shaft , an inlet board , an operating handle , and a current transformer The isolation bracket is fixed on the mechanism box, and the terminal of the circuit breaker is used as a fulcrum of the knives to form one end of the isolation fracture. The other end of the fracture opening and closing the knife gate by operating the insulator and the drive shaft. The three-phase linkage has obvious visible fractures in the state of opening of the isolating switch, and has a reliable anti-error mechanism interlocking with the main body of the circuit breaker, which is convenient and safe to maintain.

4.4 isolation switch operation sequence

4.4.1 Closing operation (power transmission operation)

    a ) Pull the isolation switch operating handle, close the isolation knife, and close it in place;

    b ) Pull the circuit breaker energy storage handle (the motoring mechanism is closed);

    c ) Pull down the circuit breaker closing pull ring and close the circuit breaker (the motor mechanism does not have this step).

4.4.2 Opening operation (manual power failure, maintenance operation)

) Pull down the circuit breaker opening pull ring and open the circuit breaker;

) Check the line side of the circuit breaker and confirm that there is no power.

) Pull the isolation switch operating handle, open the isolation knife, and open it in place.

4.4.3 Notes

) It is strictly forbidden to separate the isolating switch when the circuit breaker is closed;

) The isolating switch must be in place, otherwise the circuit breaker must not be opened or closed.

c)  Before the manual opening, it must be confirmed that there is no electricity on the outlet side of the circuit breaker.

5. Transportation, commissioning and installation

5.1 The product shall not be turned over or inverted during transportation, and anti-seismic measures shall be taken. When lifting the circuit breaker, the four earrings on the box must be hooked up. Do not carry the epoxy insulation sleeve directly.

5.2 After unpacking, check whether the outdoor epoxy insulation sleeve of the circuit breaker on the column is broken, whether the box is deformed, whether the indication is complete, whether the product nameplate and certificate are consistent with the order form, and whether the packing list is consistent with the physical object.

5.3 Before the circuit breaker is put into operation, it should be carefully checked whether the rated voltage and rated current of each operating component are consistent with the actual conditions.

5.4 The contact parameters and mechanical characteristics of the circuit breaker have been adjusted at the factory inspection, and the user does not have to open the box for inspection. After the pressure test is carried out as required, it can be installed. It is possible to perform mechanical property inspection in accordance with the requirements of Table .

5.5 The circuit breaker can be erected on a single pole or double pole. The circuit breaker should be installed smoothly and firmly on the special steel frame (as shown in Figure 3).

 

 

 

 

 

 

Preparation before installation 
fitting process based on the selected installation fittings and external processing installation PT bracket mounted attachment fittings detailed processing size in FIG. ready to install accessories The following is a number of attachments required for a single piece of equipment: 1) High-voltage dischargers . 6 th power source side and load side . 3 th 2) 10KV insulator size and number and size of the installation according to the set of poles ) ; 3) hoop size and number and size of the installation according to the set of poles ); 4) a switch outgoing cable clamp . 6 th specific dimensions of the line may be field diameter ); 5) the ground wire. 6) PT bracket. Check the appearance of the equipment to be inspected: 1) Is the fastening and sealing intact ?












2) Is there 
any damage to the bushing and the housing 
3) Is the 
control socket and the pin intact 
4) Is the 
operating handle and the split pointer in the normal position 
Insulation measurement content: 1) Insulation resistance: once to the second and ground: ≥10000MQ ; secondary to ground: ≥10MQ 2) Insulation withstand voltage: once to the second and ground: 42KV, 1min ; secondary to ground: 2KV 1min ;

Installation Step 1 : Install the circuit breaker bracket and install the PT bracket.


Step 2: Place the switch in the opening position before lifting and lifting; Note: * The length of the wire hooked on the hook should be 0.8m Pay attention to the protection switch during the lifting process to avoid damage to the casing and casing. ; * The switch allows for a slight tilt. Step 3: After lifting the circuit breaker to a position slightly higher than the horizontal crossbar of the mounting bracket, place the circuit breaker on the horizontal cross arm of the mounting bracket and fasten it with four sets of M12x60 stainless steel bolts and nuts. After confirming that the fixing is in good condition, untie the lifting wire.






Place the external PT on the lower PT mounting bracket of the circuit breaker and fasten it with sets of M14x40 stainless steel bolts and nuts. Step 4: Connection of the primary cable 1) When the isolation switch is not required to be installed on the primary line, the outlets on both sides of the circuit breaker can be directly connected to the line by the clamp. If the isolation switch is required to be installed on the primary line, the copper terminal is used. Connect the line to the exit side of the isolation knife gate. 2) Use two insulated high-voltage wires of about 10 square inches or more to connect the AB phase on the power supply side , and the other end to the high-voltage side terminal of the PT Note: Note that the insulation spacing between the cables of each phase is at least 100mm. the above;




* The circuit breaker is not less than 6.5 meters from the ground  * The distance between the PT and the circuit breaker is not less than 1.5 meters. 
Be sure to install lightning arresters on both sides of each phase of the switch to prevent damage to the equipment caused by lightning.

If the controller is not less than 2.5 meters from the ground

 

 

 

 

 

 

6. Product maintenance and maintenance

6.1 The circuit breaker on this column ensures the user's medium and long-term maintenance-free operation due to its special design structure. It only needs to perform the power frequency withstand voltage test every three years or so.

6.2 Users are not allowed to replace the electrical components that are inconsistent with the original model specifications.

6.3 The operator should have a preliminary understanding of the performance of the organization and the knowledge of installation adjustment and maintenance. The problems in operation should be recorded and the manufacturer should be notified if necessary.

7. Random files

7.1 One product certificate.

7.2 Install a copy of the instruction manual.

7.3 One packing list.

7.4 A copy of the factory inspection report.

8. Ordering Information

When ordering, please specify the model, name, quantity, rated current, rated breaking current, current transformer current ratio, operating mode and operating voltage.

Notes

9.1 It is  strictly forbidden to reverse the polarity of the DC screen power supply and the capacitive storage capacity, or directly short-circuit the output end of the closing and closing coil or connect with the positive and negative terminals of the operating power supply. Otherwise, the controller will be damaged and all consequences will be responsible for it.

9.2 It is  strictly forbidden to use the output power of the controller to supply power to other electrical equipment.

9.3  Controller wiring must be reliable, especially the opening and closing coil leads, otherwise it is easy to arc damage the controller.

9.4 When using the storage capacitor, the AC220V power input must be connected to the current limiting resistor or reactor to charge the capacitor.

9.5  Directly use DC screen power supply, connect the positive and negative poles of the power supply directly to the corresponding input terminals of the original storage capacitor.

9.6 The  controller does a long-term closing test. It is recommended that no more than three points per minute.

9.7  This controller is a precision electronic product. It is strictly forbidden to disassemble it by itself. If there is any problem, return it to our company for processing.

9.8  With the improvement of technology and the improvement and improvement of power distribution requirements, there will be improvements and differences in the future specifications. The revised content will be subject to change without prior notice.

 

 

Delivery date

location

project name

Project Number

product name

Outdoor high voltage permanent magnet column vacuum circuit breaker

Product number

NK3S-12 630A/1250A--20/31.5

Rated voltage

10KV

Rated current

630A/1250A

Breaking short circuit current (4S)

20KA/31.5KA

Close short circuit current (4S)

50KA/80KA

Operating mechanism

Permanent magnet

Number of PT

Outdoor type . 1 only   AC 220V / 50Hz

Current transformer ratio

Shell outer phase CT400:5 (10P20),

Switch housing

stainless steel

PT and switch (2.5 square )cable length

meters

Altitude

1km

Controller position

Built in

Controller function

Over flow protection 

way of communication

no

LCD remote control

no

Small remote control

Have

Neutral grounding method

Ungrounded

Load side capacity

1250kVA