Outdoor 12KV/24KV/36/40.5KV potential transformer

 Outdoor high voltage 12KV/24KV/35KV/36KV/38KV/40.5KV potential transformer OEM/ODM switch circuit breaker operating power supply, output AC220V  

 
JDZ(X)W-35(G) type potential transformer is made of vacuum-casting with outdoor special epoxy resin with arc resistance, UV resistance and aging resistance. The fully enclosed pillar structure is resistant to pollution and moisture. JDZXW-35G transformer does not require special maintenance. It only needs to clean the surface dirt regularly. Because the transformer is fully enclosed and insulated, it is small in size and light in weight. It is suitable for any position and installation in any direction. The secondary output terminal of the transformer is metal. The protective cover is sealed. AC 220V operating power supply, rated output 30VA, limit output 1kva.
 
The outdoor potential transformer  is an outdoor epoxy resin insulated and fully enclosed structure. It is suitable for power metering, voltage monitoring and relay protection in power systems with rated frequency of 50HZ or 60HZ and rated voltage of 35KV. This product complies with IEC6044 and GB1207-2006 "potential transformer" standard.

Model meaning
 
 

 

 JDZW-35G outdoor epoxy casting and silicone rubber shell composite insulated potential transformer
J--------------potential transformer
  D------------ single phase
     Z----------- epoxy casting
        W--------Outdoor installation
              35---rated voltage (kV)
                   G-with high voltage side fuse
 
 
Conditions of Use

1. Ambient temperature: -25 °C~ ~+40 °C

2. Pollution level: Level IV

Technical Parameters

1. Technical parameters are shown in the table

2. The partial discharge level conforms to the GB1207-2006 "potential transformer" standard.
 
 
 
 
Precautions:

1. The secondary winding must not be short-circuited or overloaded during use.

2. The potential transformer is closed insulation structure, only the induction withstand voltage test; the built-in voltage transformer switch, when the power frequency test, the transformer should be disconnected from the switch
 
 
model Rated voltage ratio Rated output Limit output Rated insulation level
0.2 0.5 6P
JDZW-35 Figure 1 - Figure 2 35000/100 60 150   1200 40.5/95/200
JDZW-35 Figure 3 - Figure 4 35000/100/100 30/40 60/60   2×600
JDZXW-35G Figure 5 35000/√3/100/√3/100/3 50 90 100 1000
JDZXW-35G Figure 6 35000/√3/100/√3/100/3√3/100/3 30 30 100 2×500
 
 
 
 
JDZW-20R type potential transformer is made of vacuum-proof, outdoor-resistant epoxy resin with arc resistance, UV resistance and aging resistance. The fully enclosed pillar structure is resistant to pollution and moisture. JDZW-20R transformer does not require special maintenance. It only needs to clean the surface dirt regularly. Because the transformer is fully enclosed and insulated, it is small in size and light in weight. It is suitable for any position and installation in any direction. The secondary terminal of the transformer is metal. The protective cover is sealed. AC 220V operating power supply, rated output 30VA, limit output 1kva.
 
The outdoor potential transformer is an outdoor epoxy resin insulated and fully enclosed structure. It is suitable for power metering, voltage monitoring and relay protection in power systems with rated frequency of 50HZ or 60HZ and rated voltage of 35KV. This product complies with IEC6044 and GB1207-2006 "Voltage Transformer" standard.

Model meaning
 
 

 

 JDZW-20R outdoor epoxy casting and silicone rubber shell composite insulated potential transformer
J--------------potential transformer
  D------------ single phase
     Z----------- epoxy casting
        W--------Outdoor installation
              20---rated voltage (kV)
                   R-with high voltage side fuse
 
 
Conditions of Use

1. Ambient temperature: -25 °C ~ +40 °C

2. Pollution level: Level IV

Technical Parameters

1. Technical parameters are shown in the table

2. The partial discharge level conforms to the GB1207-2006 "potential transformer" standard.
 
 
 
 
Precautions:

1. The secondary winding must not be short-circuited or overloaded during use.

2. The potential transformer  is closed insulation structure, only the induction withstand voltage test; the built-in potential transformer  switch, when the power frequency test, the transformer should be disconnected from the switch
 
 
 
model Rated voltage ratio Rated output Limit output Rated insulation level
0.2 0.5 6P
JDZW-20R 20000/100 40 100   800 24/65/125
JDZW-20R 20000/100/100 20/30 30/30   2×400
           
 
 

 Outdoor high voltage 12KV/24KV/35KV/40.5KV potential transformer switch circuit breaker operating power supply, output AC220V  

The power supply is required to operate the high voltage circuit breaker/switch. The operating current can be externally connected to AC or DC 220V power supply, but generally it is externally operated on the 12KV/24KV/40.5KV line to operate the power transformer or  potential transformer to obtain AC 220V operating power supply, rated output 30VA, limit output 1kva.

 

  
 
JDZW-10R outdoor epoxy casting and silicone rubber shell composite insulated potential transformer
J--------------potential transformer
  D------------ single phase
     Z----------- epoxy casting
        W--------Outdoor installation
              10---rated voltage (kV)
                   R-with high voltage side fuse
 
Conditions of Use

1. Ambient temperature: -250C~+400C

2. Pollution level: Level IV

Technical Parameters

1. Technical parameters are shown in the table

2. The partial discharge level conforms to the GB1207-2006 "potential transformer" standard.
 
 
 
 
Precautions:

1. The secondary winding must not be short-circuited or overloaded during use.

2. The  potential transformer is closed insulation structure, only the induction withstand voltage test; the built-in potential transformer switch, when the power frequency test, the transformer should be disconnected from the switch

 
 
 
 
 
 
 
 
 
 
Weight 45KG creepage distance 580mm