PRODUCT
CONTACT
  • ADDRESS:No.111 NanJing Road Shibi Industrial Area Panyu District of GuangZhou GuangDong,P.R.China
  • TEL:+86 20 83687691
  • FAX:+86 20 83687779
  • Email:nkautomatic@126.com
 
Lightning protector power supply surge protection>

 

ABY-FA ABY-FB (S)
Power lightning protection module series (100kA)

ABY-FA  ABY-FB(S)
电源防雷模块系列(100ka)

 The main features:
Through flow capacity, the maximum can reach 100kA.
Modular design, easy installation, simple maintenance.
Based on the modules can be combined, lightning protection device conforms to the user demand phase number and lightning protection box, high flame retardant shell material.
By control circuit technology, to avoid the fire.
With remote alarm contact (at the same time have a normally open and normally closed contacts) convenient remote monitoring (FBS).
Fast response time.

 

主要特点:

   通流容量大,最大可达100kA。

   模块式设计、安装方便、维护简单。

   以模块为基础,可组合出符合
用户需求相数的防雷器和防雷箱
,高阻燃外壳材料。

   采用温控断路技术,避免火灾发生。

   带远程告警接点(同时拥有常开、常闭触点)方便远程监视(FBS) 。

   响应时间快。 


Technical parameters: 技术参数:

Model 型号
ABY-FA
ABY-FB(S)
Maximum continuous operating voltage
最大持续工作电压
420Vac
385Vac
The maximum flow capacity
最大通流容量(8/20 uS))
100kA(10/350uS)
150kA(8/20uS)
Response time 响应时间
<100ns
<25ns
The level of protection  保护水平
3500V
3000V
Installation method 安装方式
35mm din Rail 导轨


 Installation method:
1, wiring diagram as shown in Fig.
2, the power supply connection wires for not less than 6 mm multi strand copper wire, grounding wire with not less than 10 mm multi strand copper wire, connecting line should be short, straight, thick.
3, lightning protection device front end series suitable fuse or breaker.


Installation notes:
1, the installation must be disconnected from the power supply, strictly charged operation, connecting wires must meet the requirements.
2, lightning protection device does not need special maintenance, only need to regularly check the connection status indicating whether there is loose, whether it is normal.
3, when the lightning protection module fault display window indicates red remote signal terminal output alarm signal (FBS) said the lightning protection device failure, should be promptly replaced.
4, after installation, the lightning protection module is inserted in the end, check whether the normal work. 932

 

 

 

  1、接线图如图所示

  2、电源连接导线用不小于6平方毫米的多股铜线,接地线用不小于10平方毫米的多股铜线,连接线应尽量的短、直、粗。

  3、防雷器前端应串联合适的熔断器或空开

 

安装注意事项:

  1、安装时必须断开电源,严禁带电操作,连接导线必须符合要求。

  2、防雷器无须特别维护,只需定期检查其连接是否有松动,状态指示是否正常。

  3、当防雷器模块故障显示窗口指示红色时遥信端子输出告警信号(FBS)则表示防雷器发生故障,应及时更换

  4、安装完毕后,将防雷模块插到底,检查工作是否正常。932

 


 

 

 

 

安装方法: