PRODUCT
CONTACT
  • ADDRESS:No.111 NanJing Road Shibi Industrial Area Panyu District of GuangZhou GuangDong,P.R.China
  • TEL:+86 20 83687691
  • FAX:+86 20 83687779
  • Email:nkautomatic@126.com
 
Three phase power arrester protection box>

Three phase power lightning arrester for lightning protection box series ABY-380ZJ/150

三相电源防雷器防雷箱系列ABY-380ZJ/150

ABY-380ZJ/150 series three-phase power supply lightning protection box

ABY-380ZJ/150   三相电源防雷箱系列

 The main features:
With lightning counting function
With a strong anti lightning and overvoltage in operation ability
With continuous lightning proof ability
Intelligent quantitative failure indication with
Do not need to loop is serially connected with a fuse or breaker
With large flow capacity (increased 50kA through flow capacity standby)

主要特点:

   具有雷电计数功能

   具有极强的抗雷击与操作过电压能力

   具有连续防雷击能力

   具有智能型定量失效指示

   不需要回路上串接熔断器或空气开关

   具有超大通流能力(增加50kA通流容量备用)

Status indication:
150kA: indicator light, said lightning protection box corresponding to the actual maximum through phase flow is 125kA ~ 150kA.
125kA: indicator light, said lightning protection box corresponding to the actual maximum through phase flow is 100kA ~ 125kA.
100kA: indicator light, said lightning protection box corresponding to the actual maximum through phase flow is 95kA ~ 100kA.
95kA: indicator light, said lightning protection box corresponding phase of the actual maximum through flow rate of 95kA, and provides the remote communication switch signal, that part of the lightning protection box components has been damaged by lightning protection box has not reached to the maximum flow rate, must be replaced.

状态指示:

  150kA:指示灯亮时,表示防雷箱对应相的实际最大通流量为125kA~150kA之间。

  125kA:指示灯亮时,表示防雷箱对应相的实际最大通流量为100kA~125kA之间。

  100kA:指示灯亮时,表示防雷箱对应相的实际最大通流量为95kA~100kA之间

  95kA:指示灯亮时,表示防雷箱对应相的实际最大通流量为95kA,并提供遥信开关信号,说明防雷箱内的部分元件已损坏,防雷箱已达不到最大通流量,必须更换

 

Technical parameter 技术参数:

Model 型号
ABY-380ZJ/150  
Maximum continuous operating voltage
最大持续工作电压
385Vac  
Rate voltage 标准工作电压
220/380Vac  
work rate 工作频率
50HZ  
The nominal current capacity
标称通流容量(8/20 uS)
100kA  
Through flow capacity limit
极限通流容量(8/20 uS)
150kA  
Limit voltage 限制电压
1500V  
response time 响应时间
<25nS  
Protected mode 保护模式(3+1)
L-N; N-PE  
The wiring terminal 接线端子
最大35平方毫米  
work environment 工作环境
工作温度-40℃~+80℃;相对湿度:95%(25℃)  
earth resistance 接地电阻
≤4Ω  

Note: must be greater than or equal to 10 square mm access wire, grounding is more than 16 square mm, otherwise it will cause line fault.
Installation method:
1, lightning protection box can be hung on a wall, can also be flat, into line underneath.
2, using direct parallel connection mode as shown in the diagram, but should pay attention to the connection wire to day short, straight, thick.
Installation notes:
The installation must be disconnected from the power supply, strictly charged operation, connecting wires must meet the requirements.

 

934
注:接入导线必须≥10平方毫米,接地≥16平方毫米,否则将引起导线故障。

安装方法:

  1、防雷箱既可以壁挂,也可以平放,引入线在下方

  2、采用如图所示的直接并联的接线方式,但应注意连接导线要昼的短、直、粗。

安装注意事项:

  安装时必须断开电源,严禁带电操作,连接导线必须符合要求。